Determination of the economical optimum insulation thickness for VRF (variable refrigerant flow) systems


YILDIZ A., Ali Ersöz M.

Energy, cilt.89, ss.835-844, 2015 (SCI-Expanded) identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 89
  • Basım Tarihi: 2015
  • Doi Numarası: 10.1016/j.energy.2015.06.020
  • Dergi Adı: Energy
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus
  • Sayfa Sayıları: ss.835-844
  • Anahtar Kelimeler: Life-cycle analysis, Optimum insulation thickness, Variable refrigerant flow
  • Uşak Üniversitesi Adresli: Evet

Özet

This study deals with the investigation into optimum insulation thickness of installed inside building pipe network of VRF (variable refrigerant flow) systems. Optimum insulation thickness, energy savings over a lifetime of 10 years and payback periods are determined for high pressure gas pipelines, low pressure gas pipelines and low pressure liquid pipelines under the heating-only and cooling-only modes of the three-pipe VRF system using R-410A as refrigerant. By using the P1-P2 method, the value of the amount of the net energy savings is calculated. Under heating mode of VRF system, while the optimum insulation thickness varies between 16 and 20 mm depending on the pipe sections of high pressure gas pipeline, it varies from 11 to 13 mm for the pipe sections of low pressure liquid pipeline. Under cooling mode of VRF system, the optimum insulation thickness varies between 7 and 8 mm for pipe sections of low pressure gas pipeline and low pressure liquid pipeline.